Research Article

Dynamic Simulations of the Allam Cycle Power Plant Integrated with an Air Separation Unit

Table 5

Controller specifications of the integrated Allam power plant/ASU.

Controller IDController typePVMVTuning parameters
KC (%/%)τi (min)

PIC-1PIHPC column pressureCondenser heat duty (CV-1 VP)2012
LIC-1PIHPC sump liquid levelHPC bottom flowrate (CV-8 VP)1060
LIC-2PIHPC condenser liquid levelHPC top flowrate (CV-9 VP)1060
PIC-2PILPC column pressureLPC top flowrate (CV-2 VP)2010
LIC-3PILPC sump liquid levelLPC bottom flowrate (CV-7 VP)1060
AIC-1PICombustor outlet methane slipRSP to RC-10.010.5
RC-1PING/air ratio (in mass flow)CV-10 VP120
FIC-2PING (in mass flow)CV-6 V P120
TIC-1PICombustor outlet temperatureRecycled CO2 flow (CV-5 VP)0.8751.99
PIC-3PISeparator top pressureCOMP in flow rate (CV-3 VP)2012
LIC-4PISeparator liquid levelWater mass flow rate (CV-4 VP)1060

PV: process variable; MV: manipulated variable; CV: control valve; VP: valve position; RSP: remote set point.