Research Article
Energy Consumption Analysis of a Large Building at Memorial University
Table 1
Energy report for the building.
| | Input data Report | Building envelope | Windows |
| Project | Building | Building | Area [m2] | U [W/(m2 K)] | UA [W/K] | % of total | Side | Area [m2] | U Glass [W/(m2 K)] | U Frame [W/(m2 K)] | U Total [W/(m2 K)] | UA [W/K] |
| Customer | | Model floor area | 25141.7 m2 | Walls above ground | 7450.19 | 0.54 | 4002.24 | 44.85 | N | 174.36 | 2.86 | 2 | 2.77 | 483.51 |
| Created by | Almahdi Abdo-Allah | Model volume | 128952.9 m3 | Roof | 10529.8 | 0.17 | 1811.13 | 20.3 | E | 131.08 | 2.86 | 2 | 2.77 | 363.49 |
| Location | Newfoundland (St. John’s Airport)_718010 | Model ground area | 10544.5 m2 | Windows | 713.73 | 2.77 | 1979.24 | 22.18 | S | 213.24 | 2.86 | 2 | 2.77 | 591.35 |
| Climate file | CAN_NF_St.Johns.7180 10_CWEC | Model envelope area | 29440.0 m2 | Doors | 201.72 | 0.59 | 118.38 | 1.33 | W | 195.05 | 2.86 | 2 | 2.77 | 540.89 |
| Case | building2017_AHU8 | Average U-value | 0.3031 W/(m2 K) | Walls below ground | 0 | 0 | 0 | 0 | Total | 713.73 | 2.86 | 2 | 2.77 | 1979.24 |
| Simulated | 1/19/2017 22:04 | Envelope area per Volume | 0.2283 m2/m3 | Floor towards ground | 10544.5 | 0.09 | 991.82 | 11.11 | | | | | | |
| | | | | Total | 18567.2 | 0.41 | 7689.82 | 100 | | | | | | |
|
|