Research Article

Enhancing Distribution System Performance via Distributed Generation Placement and Reconfiguration Based on Improved Symbiotic Organisms Search

Table 1

Comparisons of ISOS and other techniques in solving 33-node system.

ItemsOpened switchesPDG (kW)/(node)Power losses (kW)Power loss reduction (%)Minimum voltage magnitude (pu)

Original case33-34-35-36-37202.660.9131
ISOS7-14-9-30-28739/(33)
469/(12)
1020/(25)
54.478573.12060.9678
SOS7-14-9-31-28544/(12)
530/(18)
1145/(25)
55.282472.72390.9689
FF [17]8-9-28-32-33841/(31)
340/(32)
591/(33)
73.9563.510.9735
ISCA [18]7-9-14-28-31648/(30)
510/(13)
532/(16)
66.8167.030.9611
FWA [19]7-11-14-28-32536/(32)
615/(29)
531/(18)
67.1166.890.9713
HSA [20]4-7-10-28-32525/(32)
558/(31)
584/(33)
73.0563.950.9700
GA [20]7-10-28-32-3475.1362.920.9766
RGA [20]7-9-12-27-3274.3263.330.9691
EOA [21]8-27-33-34-36165/(8)
651/(14)
1413/(29)
61.4869.66
IEOA [21]7-10-13-27-31399/(8)
669/(17)
1160/(29)
57.4071.67