Operational Risk Assessment of Distribution Network Equipment Based on Rough Set and D-S Evidence Theory
Table 8
Fault diagnosis using Rogers ratio method.
| | | | | Diagnosis |
| 0 | 0 | 0 | 0 | Normal aging | 3 | 0 | 0 | 0 | Partial discharge (corona) | 1~2 | 0 | 0 | 0 | Overheating (≤150°C) | 1~2 | 1 | 0 | 0 | Overheating (150°C~200°C) | 0 | 1 | 0 | 0 | Overheating (200°C~300°C) | 0 | 0 | 1 | 0 | Metal superheating | 1 | 0 | 1 | 0 | Circular current in coil | 1 | 0 | 2 | 0 | Circular current in iron core and shell or joint overload | 0 | 0 | 0 | 1 | Arc discharge-no perfoliate discharge | 0 | 0 | 1~2 | 1 | Arc discharge-perfoliate discharge | 0 | 0 | 2 | 2 | Continuous discharge breakdowns | 3 | 0 | 0 | 1~2 | Partial discharge-corona (sign of creepage) |
|
|