Dynamic Performance Improvement Using Model Reference Adaptive Control of Photovoltaic Systems under Fast-Changing Atmospheric Conditions
Table 4
Dynamic quantitative comparative analysis of the different MPPT control algorithms.
| Criteria for evaluation | P&O [23] | INC [27] | VSINC [39] | PSO [48] | GWO [49] | MRAC |
| Response time under normal test conditions | 0.05 s | 0.02 s | 0.03 s | 0.1 s | 0.04 s | 0.01 s | Response time under rapidly changing atmospheric conditions | 0.04 s | 0.01 s | 0.02 s | 0.09 s | 0.03 s | 0.009 s | Maximum PV voltage | 17.76 V | 17.37 V | 17.65 V | 17.52 V | 16.87 V | 17.58 V | Maximum PV current | 07.33 A | 07.48 A | 07.38 A | 07.43 A | 07.451 A | 07.41 A | Maximum PV power | 130.3 W | 130 W | 130.3 W | 130.3 W | 130.3 W | 130.3 W | Efficiency (%) | 99.09 | 98.69 | 99.71 | 99.54 | 98.97 | 99.88 |
|
|