Research Article

Deadbeat Control of a Modified Single-Phase Five-Level Photovoltaic Inverter with Reduced Number of Switches

Table 6

Standard limit and individual harmonic of Γu inverter.

Even harmonicOdd harmonic
Harmonic orderIEC62040-3%Γu inverter %Harmonic orderIEC62040-3%Γu inverter %

220.11350.66
410.24561
60.50.14751.02
80.50.1291.50.71
100.20.09113.50.38
120.20.051330.12
140.20.09150.30.14
160.20.041720.11
180.20.06191.50.09
200.20.03210.20.05
220.20.03231.50.06
240.20.03251.50.03