Test data of 20 transformers rated between 20MVA and 175MVA (88 kV–420 kV).

Tx noYear of installationH2 (ppm)CH4 (ppm)C2H2 (ppm)C2H6 (ppm)C2H4 (ppm)CO2 (ppm)CO (ppm)Furans (ppm)Moisture (ppm)Acidity (mg KOH/g)BDV (kV)DDF (%)IFT (dynes/ cm)ColourHST (°C)Load (pu)

Tx1199623430052562954957000.25220.07520.14301.5600.58
Tx260711932576720111891.37230.13440.264242610.6
Tx3199632.545.81725.5421.3136856970.4916.50.058610.174272490.57
Tx4198674347351941722278981974.5280.18400.266202.5780.61
Tx57165181277945675821.1190.15380.185232.5580.44
Tx620001071290556870388920.1260.09480.249251.5660.65
Tx71981979236112183180249218435.7623.20.25151.70.458263750.72
Tx819761498395263233951237115823.9330.19350.593254660.48
Tx919962947486212134867646690.8390.08490.1352.5770.75
Tx101631069298151723482994.48420.22460.221213.5640.45
Tx111998151881511023232970.2260.13640.566272680.5
Tx126783681639210811391620.16110.05700.113381810.82
Tx132015893724161818832420.0390.04710.068450560.55
Tx141995195660221277933473560.0960.03660.207411530.6
Tx151990440522183316253826850.31120.05650.319282500.66
Tx16201015809571359020.1100.03550.15421610.44
Tx17200511764141049916370.83100.09620.733291.5530.5
Tx184416785573621334516955.1320.25550.328263770.62
Tx192000754401061378462612.4400.092310.416223610.55
Tx2020021817921.15629713192.68.9121.20.34933.50.257203500.5