Research Article

Multiparameter-Based Fuzzy Logic Health Index Assessment for Oil-Immersed Power Transformers

Table 1

Oil quality parameters.

Serial no.Oil quality parameterTesting method/instrumentStandards

1Breakdown voltage (kV)Megger OTS100AF and Foster OSTS100F (0–100 kV)IEC 60156

2Water content moisture (ppm)Karl Fischer Titration (KFT) method Moisture-in-oil sensorASTM D1533

3AcidityChemistry neutralization methodASTM D947

4Colour and appearanceTransmitted light and visual inspectionIEC-ISO 2049 ASTMD-1524

5Dielectric dissipation factor (DDF)Oil tan delta & resistivity test kit ex. MOTRIEC 60247

6Interfacial tension (IFT)TensiometerASTM D-971